J041--Glycol Addition for Main Chiller Loop
Agency: | |
---|---|
Level of Government: | Federal |
Category: |
|
Opps ID: | NBD00159085060763044 |
Posted Date: | Mar 18, 2024 |
Due Date: | Mar 8, 2024 |
Source: | https://sam.gov/opp/95cd643043... |
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Presolicitation (Updated)
- All Dates/Times are: (UTC-06:00) MOUNTAIN STANDARD TIME, DENVER, USA
- Updated Published Date: Mar 18, 2024 08:26 am MDT
- Original Published Date: Mar 18, 2024 08:16 am MDT
- Updated Response Date: Mar 08, 2024 05:00 pm MST
- Original Response Date: Mar 08, 2024 05:00 pm MST
- Inactive Policy: Manual
- Updated Inactive Date: Apr 07, 2024
- Original Inactive Date: Apr 07, 2024
-
Initiative:
- None
- Original Set Aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
- Product Service Code: J041 - MAINT/REPAIR/REBUILD OF EQUIPMENT- REFRIGERATION, AIR CONDITIONING, AND AIR CIRCULATING EQUIPMENT
-
NAICS Code:
- 238220 - Plumbing, Heating, and Air-Conditioning Contractors
-
Place of Performance:
Northern Arizona VA Healthcare System (NAVAHCS) Bob Stump Department of VA Medical Center Prescott , AZ 86313USA
Contractor will be required to perform the addition of propylene glycol into the main chiller plant. The chiller plant requires about 6,000 gallons of glycol to be added to the system to maintain the 30% protection to prevent the system from freezing. The proper percentage of glycol allows the system to operate at the proper performance levels. The main chiller system for the facility also acts as a secondary system for the MRI chiller if a failure would occur, the main chiller system would engage and provide the operational protection for the MRI system.
The current closed loop system of the main chiller system is estimated at 20,000 gallons. The estimated amount of glycol for 30% performance and freeze protection would require about 6,000 gallons to be injected or added to the system. The contractor would add corrosion inhibitor (800ppm of Sodium Nitrite) for the prevention of corrosion and a micro biocide would be added for the prevention of microbiological growth.
Solicitation shall be issued at a later date. The following NAICS code: 238220 and FSC code: J041 apply to this requirement.
This is a 100% Service Disabled Veteran-Owned Small Business (SDVOSB) set-aside. ALL SDVOSB s MUST BE CERTIFIED WITH THE GOVERNMENT. All interested parties must respond to the solicitation announcement. A response to this notice is not a request to be added to a prospective bidders list or to receive a copy of the solicitation. Telephone responses will not be accepted. Point of Contact for this announcement is Jamie ElBedawi at Jamie.elbedawi@va.gov.
- 335 E. German Rd SUITE 301
- Gilbert , AZ 85297
- USA
- ElBedawi, Jamie
- jamie.elbedawi@va.gov
- Mar 18, 2024 08:26 am MDTPresolicitation (Updated)